Simulink onramp 3.1 represent power systems components task 5 error

me esta dando este error la tarea, pero se ha hecho todo desde el inicio correctamente
Simulink onramp 3.1 represent power systems components task 5 error

 Akzeptierte Antwort

Shivam Gothi
Shivam Gothi am 2 Dez. 2024

9 Stimmen

As per my understanding, you have completed tasks 1-4 of Power Systems Simulation Onramp successfully, but not able to complete task-5, even after following all the instructions carefully.
I also encountered same issue, but resolved it in the following way:
  • The block "Wye-Connected Load" is to be configured as a "series RL" load.
  • But, by default, it also models stray capacitance. You can verify this by going to the "Parasitics" drop-down found in the "block parameters" of "Wye-Connected Load". You can see that "Parasitic Parallel Conductance" is set to its default value of 1e-6.
  • Change the "Parasitic Parallel Conductance" to the value of "0" as shown below:
After making the above change, submit the task-5 by clicking "submit" button. You will see that your test is now passed as shown below:
I hope you find this useful !!

4 Kommentare

Thanks Shivam Gothi for the response, that task already worked for me with your recommendation, thank you very much for your answers.
@Shivam Gothi, muchas gracias por compartir esta información, llevaba dos días intentando hacer esa actividad y no habia podido

Melden Sie sich an, um zu kommentieren.

Weitere Antworten (1)

Ruisong
Ruisong am 25 Apr. 2025

0 Stimmen

I met this issue as well and the answer here works for me