How are centrifugal pump(TL) outlet flow rate and actual brake power calculated with pump nominal parameters?
41 Ansichten (letzte 30 Tage)
Ältere Kommentare anzeigen
도상 이
am 13 Nov. 2024 um 5:04
Beantwortet: Yifeng Tang
am 20 Nov. 2024 um 14:54
Hello,
I am currently working on a data center cooling example using Simscape Fluids. I am trying to understand how the outlet flow rate and the actual brake power of the Centrifugal Pump (TL) are determined based on the Input Angular Velocity (RPM) and the Nominal Parameters and Reference Shaft Speed specified when selecting 'Capacity, head, and brake power at reference shaft speed' within the Centrifugal Pump (TL) block.
I am aware from the block's help documentation that the values are determined according to the affinity laws. However, the equations provided in the help center do not clearly explain how the outlet flow rate is determined based on my specific input RPM relative to the nominal values.
Could someone provide a detailed explanation of the relationship between the Nominal Values, Reference Values, and the values measurable through sensors? And also is there any functions or source codes to expect the output values?
Thank you for your assistance.
0 Kommentare
Akzeptierte Antwort
Yifeng Tang
am 20 Nov. 2024 um 14:54
In the equation for the reference capacity: , the first term on the RHS is the volumetric flow rate.
If you move that term to the left, this is the equation of flow rate calculated from RPM (ω) and other nominal values.
0 Kommentare
Weitere Antworten (0)