NI DAQ channel terminal in MATLAB is read-only
7 Ansichten (letzte 30 Tage)
Ältere Kommentare anzeigen
Hyalex Ortho
am 27 Feb. 2023
Beantwortet: Hyalex Ortho
am 1 Mär. 2023
Hello, I am using an NI-9422 to read in a signal for motor speed. I am reading in through the data acquisition toolbox in MATLAB. I can read the frequency fine for 1 terminal but I am struggling to understand how to read multiple terminals or a specific terminal.
For instance, the current assigned terminal is PFI5 and if I try to assign a variable ch to my channel and then re-assign the ch.terminal as PFI7 it says it's read only. I've also unplugged, and plugged the chassis back in and the default terminal changes which I can only solve by moving my wires.
What am I missing? Thanks for any help.
0 Kommentare
Akzeptierte Antwort
Weitere Antworten (1)
chrisw23
am 28 Feb. 2023
As long as the PFI is configured as Input it should be readOnly.
Each PFI line can be individually configured as a static digital input or a static digital output.
Check the current I/O state.
4 Kommentare
chrisw23
am 1 Mär. 2023
I'm not using the DataAcqToolbox but the DAQmx API instead but I think it is similar.
When you define the task you have to add all channels you want to use and you can't get access to a channel that is not defined for that task.
i.e.
obj.ContinuousAnalogInTask.AIChannels.CreateVoltageChannel(...
% physicalChannelName
% nameToAssignChannel (alias)
% enum NationalInstruments.DAQmx.AITerminalConfiguration
% minimumValue
% maximumValue
% NationalInstruments.DAQmx.AIVoltageUnits