three phase fault block
14 Ansichten (letzte 30 Tage)
Ältere Kommentare anzeigen
nur izzati
am 24 Mär. 2011
Beantwortet: Degam
am 13 Okt. 2023
How to use external control fault timing?
I have the algorithm to trip the breaker, but how to apply fault using the external control timing, what block that can be connected to it?
0 Kommentare
Akzeptierte Antwort
Arnaud Miege
am 24 Mär. 2011
I assume you are referring to the Three-Phase Fault block from SimPowerSystems. If you look at the documentation for the block, you'll see that it says:
External control of fault timing
If selected, adds a fourth input port to the Three-Phase Fault block for an external control of the switching times of the fault breakers. The switching times are defined by a Simulink signal (0 or 1) connected to the fourth input port of the block.
So the answer is any regular Simulink block, the signal has to be either 0 or 1.
HTH,
Arnaud
0 Kommentare
Weitere Antworten (2)
nur izzati
am 9 Jun. 2011
2 Kommentare
Arnaud Miege
am 9 Jun. 2011
Please start a new question rather than add to an existing one. Also, please provide more details: which block are you talking about? what do you mean by polarity? etc... If you have an example model to illustrate your question, even better.