Control System Designer: Inconsistent Controller Output Step Response

134 Ansichten (letzte 30 Tage)
Markus M.
Markus M. am 11 Sep. 2025 um 20:20
Kommentiert: Markus M. am 19 Sep. 2025 um 8:35
I use the control system designer with e.g simple plant and controller:
s = tf('s')
G = 1/(s+1)
C = 1/s;
controlSystemDesigner(G,C);
and the default control system architecture
After adding the step reponses
(via selection from step reponses) and
via:
I expected them to be the same responses (since du is probably 0).
The response is correct, however is wrong (unbounded) and differs from :
Is this a bug?
Best regards
Markus

Antworten (1)

Paul
Paul am 11 Sep. 2025 um 21:21
I can recreate these result and uc/r certainly looks incorrect. After exporting the systems to the base workspace I get:
>> tf(IOTransfer1)
ans =
From input "r" to output "u":
s + 1
-----------
s^2 + s + 1
Continuous-time transfer function.
Model Properties
>> tf(IOTransfer2)
ans =
From input "r" to output "uC":
s + 1
---------
s^2 + 2 s
IOTransfer2 surely is incorrect and I can't figure out how such a result was obtained.
  13 Kommentare
Paul
Paul vor etwa 15 Stunden
Have you received confirmation of bug, or other closure, from Mathworks tech support?
Markus M.
Markus M. vor etwa 10 Stunden
@Paul, yes Mathworks has confirmed this as a bug, which will be investaged and fixed. If an external bug report is published I am going to link it to this thread.