WSCC 9-bus system
9 Ansichten (letzte 30 Tage)
Ältere Kommentare anzeigen
hello,
I am ding my simulation on WSCC 9-bus to find the transient stability, with 3rd order of generator.i.e states are [delta,omega,Eq']. I did the load flow to find the operating point (at steady state) and Y admittance but I didn't get the good one. Please help me with your suggestions.
2 Kommentare
MUHAMMED FASIL
am 2 Feb. 2014
PLEASE HELP WITH Y BUS FORMATION MATLAB PROGRAM OF A WSCC 3 MACHINE 9 BUS SYSTEM
Antworten (3)
Jureddy
am 14 Feb. 2024
We illustrate the DAE models discussed in the previous sectionwith a numerical
example. We consider the popular Western System Coordinating
Council (WECC) 3-machine, 9-bus system [73] shown in Figure 7.4. This
is also the system appearing in [74] and widely used in the literature. The
base MVA is 100, and system frequency is 60 Hz. The converged load-
ow
data obtained using the EPRI-IPFLOW program [75] is given in Table 7.1.
Table 7.1: Load-Flow Results of the WECC 3-Machine, 9-Bus System
Bus # Voltage (pu) PG QG PL QL
(pu) (pu) (pu) (pu)
1 (swing) 1.04 0.716 0.27 { {
2 (P-V) 1.0256 9:3o 1.63 0.067 { {
3 (P-V) 1.0256 4:7o 0.85 -0.109 { {
4 (P-Q) 1.0266 2:2o { { { {
5 (") 0.996 6 4:0o { { 1.25 0.5
6 (") 1.0136 3:7o { { 0.9 0.3
7 (") 1.0266 3:7o { { { {
8 (") 1.0166 0:7o { { 1.00 0.35
9 (") 1.0326 2:0o { { {
0 Kommentare
Siehe auch
Kategorien
Mehr zu Power and Energy Systems finden Sie in Help Center und File Exchange
Community Treasure Hunt
Find the treasures in MATLAB Central and discover how the community can help you!