Controlled Voltage Source (Three-Phase)
1 Ansicht (letzte 30 Tage)
Ältere Kommentare anzeigen
After the three-phase voltage signal passes through the Controlled Voltage Source (Three-Phase), the amplitude becomes root three times the original value, and the phase also changes. But according to the module description:
- Instantaneous — The output voltages, [va vb vc], are equal to the values of the input port S.
The signal input and output should be same..
Could anyone help me this question? Many thanks.
3 Kommentare
Akzeptierte Antwort
nick
am 25 Jul. 2024
Bearbeitet: nick
am 25 Jul. 2024
Hi Yunzhong,
I understand that you are facing an issue with the difference in the value measured by the sensor and the original value. The reason of the discrepancy is that 'Current and Voltage Sensor" block measures phase to phase voltage by default. The phase to phase voltage is square root 3 times the phase to ground voltage.
You can change the 'Voltage measurement type' from phase-to-phase to phase-to-ground voltage. You may refer the following documentation to learn more about the "Current and Voltage Sensor" block:
Hope this helps.
2 Kommentare
Umar
am 25 Jul. 2024
So, it was the setting issue with Current and Voltage Sensor block which makes sense now because that will cause the amplitude to become root three times the original value, and the phase change when using controlled voltage source but glad to know that this issue is resolved.
Weitere Antworten (0)