Filter löschen
Filter löschen

Load flow doesn't run properly, the results in all buses are 0

10 Ansichten (letzte 30 Tage)
Javier Díez Martín
Javier Díez Martín am 11 Mai 2022
Kommentiert: Asi angel am 14 Jul. 2024 um 20:14
Hi everyone,
I am triying to obtain the load flow buses results in the load flow analyzer table but it only appears "0". Moreover, it sends an error message telling that there is no swing bus but I have a 3 phase programmable voltage source in my model. I attach an image with my simulation model.
Thank you!

Antworten (1)

Riya
Riya am 26 Dez. 2023
Bearbeitet: Riya am 5 Jan. 2024
Hello Javier,
As per my understanding, the issue you are facing is that load flow doesn't run properly and the results in all buses are 0.
Since you're getting an error message that there is no swing bus (also known as a slack bus) and all the buses in your load flow results are showing zero, here are a few steps you can take to troubleshoot the problem:
  • Check the Swing Bus Configuration:
- Ensure that your 3-phase programmable voltage source is indeed configured as a swing bus in your load flow analysis settings.
- Double-check that the swing bus is properly defined with a specified voltage magnitude and angle (usually, the angle is set to 0 degrees).
  • Check Bus Connectivity:
- Verify that all buses are correctly connected in your model. A common error is an unconnected bus that can cause the load flow to not run properly.
  • Check Component Settings:
- Review the settings of all other components in your model to ensure they are configured correctly for the load flow analysis.
- Make sure that load and generation data are correctly entered.
  • Review Load Flow Settings:
- Check the load flow analysis settings for any potential misconfigurations that could be causing the problem.
- Ensure that the load flow method (e.g., Newton-Raphson, Gauss-Seidel) is appropriate for your system.
You may refer the following resource for more information:
I hope it helps!
  1 Kommentar
Asi angel
Asi angel am 14 Jul. 2024 um 20:14
Can you help me Riya, I am trying to apply the load flow analyzer from the powergui in matlab- simulink , but when I tried to apply the load flow the result showed up before the voltage regulator , but after the voltage regulator all the buses are 0
send me plz if you can help me with this (asiangel1269@gmail.com)
** I am working on IEEE 34 DN
Thanks

Melden Sie sich an, um zu kommentieren.

Kategorien

Mehr zu Power Transmission and Distribution finden Sie in Help Center und File Exchange

Tags

Produkte

Community Treasure Hunt

Find the treasures in MATLAB Central and discover how the community can help you!

Start Hunting!

Translated by