IEEE 14 bus Power flow code
Ältere Kommentare anzeigen
Hi Anybody can send me the IEEE 14 bus power flow program.
Yunus
1 Kommentar
kalana agampodi
am 6 Okt. 2021
Chech the link. I complited it and also did fast decoupled power flow, Q limits cotrol by using Newton Raphson and using Crout's method.
Antworten (3)
Muruganandham Subramanian
am 13 Dez. 2011
function [baseMVA, bus, gen, branch, areas, gencost] = case14
%%system MVA base
baseMVA = 100;
%%bus data
% bus_i type Pd Qd Gs Bs area Vm Va baseKV zone Vmax Vmin
bus = [
1 3 0 0 0 0 1 1.06 0 0 1 1.06 0.94;
2 2 21.7 12.7 0 0 1 1.045 -4.98 0 1 1.06 0.94;
3 2 94.2 19 0 0 1 1.01 -12.72 0 1 1.06 0.94;
4 1 47.8 -3.9 0 0 1 1.019 -10.33 0 1 1.06 0.94;
5 1 7.6 1.6 0 0 1 1.02 -8.78 0 1 1.06 0.94;
6 2 11.2 7.5 0 0 1 1.07 -14.22 0 1 1.06 0.94;
7 1 0 0 0 0 1 1.062 -13.37 0 1 1.06 0.94;
8 2 0 0 0 0 1 1.09 -13.36 0 1 1.06 0.94;
9 1 29.5 16.6 0 19 1 1.056 -14.94 0 1 1.06 0.94;
10 1 9 5.8 0 0 1 1.051 -15.1 0 1 1.06 0.94;
11 1 3.5 1.8 0 0 1 1.057 -14.79 0 1 1.06 0.94;
12 1 6.1 1.6 0 0 1 1.055 -15.07 0 1 1.06 0.94;
13 1 13.5 5.8 0 0 1 1.05 -15.16 0 1 1.06 0.94;
14 1 14.9 5 0 0 1 1.036 -16.04 0 1 1.06 0.94;
];
save baseMVA baseMVA;
save bus bus;
%%generator data
% bus Pg Qg Qmax Qmin Vg mBase status Pmax Pmin
gen = [
1 232.4 -16.9 10 0 1.06 100 1 332.4 0;
2 40 42.4 50 -40 1.045 100 1 140 0;
3 0 23.4 40 0 1.01 100 1 100 0;
6 0 12.2 24 -6 1.07 100 1 100 0;
8 0 17.4 24 -6 1.09 100 1 100 0;
];
save gen gen;
%%branch data
% fbus tbus r x b rateA rateB rateC ratio angle status
branch = [
1 2 0.01938 0.05917 0.0528 9900 0 0 0 0 1;
1 5 0.05403 0.22304 0.0492 9900 0 0 0 0 1;
2 3 0.04699 0.19797 0.0438 9900 0 0 0 0 1;
2 4 0.05811 0.17632 0.034 9900 0 0 0 0 1;
2 5 0.05695 0.17388 0.0346 9900 0 0 0 0 1;
3 4 0.06701 0.17103 0.0128 9900 0 0 0 0 1;
4 5 0.01335 0.04211 0 9900 0 0 0 0 1;
4 7 0 0.20912 0 9900 0 0 0.978 0 1;
4 9 0 0.55618 0 9900 0 0 0.969 0 1;
5 6 0 0.25202 0 9900 0 0 0.932 0 1;
6 11 0.09498 0.1989 0 9900 0 0 0 0 1;
6 12 0.12291 0.25581 0 9900 0 0 0 0 1;
6 13 0.06615 0.13027 0 9900 0 0 0 0 1;
7 8 0 0.17615 0 9900 0 0 0 0 1;
7 9 0 0.11001 0 9900 0 0 0 0 1;
9 10 0.03181 0.0845 0 9900 0 0 0 0 1;
9 14 0.12711 0.27038 0 9900 0 0 0 0 1;
10 11 0.08205 0.19207 0 9900 0 0 0 0 1;
12 13 0.22092 0.19988 0 9900 0 0 0 0 1;
13 14 0.17093 0.34802 0 9900 0 0 0 0 1;
];
save branch branch;
%%----- OPF Data -----%%
%%area data
areas = [
1 1;
];
%%generator cost data
% 1 startup shutdown n x1 y1 ... xn yn
% 2 startup shutdown n c(n-1) ... c0
gencost = [
2 0 0 3 0.0430293 20 0;
2 0 0 3 0.25 20 0;
2 0 0 3 0.01 40 0;
2 0 0 3 0.01 40 0;
2 0 0 3 0.01 40 0;
];
return;
this is the data file. you just try it for powerflow solution...
8 Kommentare
Mohammad Yunus Ali
am 14 Dez. 2011
Walter Roberson
am 3 Mai 2012
Was this code copied from the MATLAB File Exchange? If so then the power flow code is there.
jasmin donga
am 28 Jul. 2016
Walter Roberson
am 28 Jul. 2016
Bearbeitet: Walter Roberson
am 27 Jul. 2021
ezekiel gandham
am 2 Dez. 2017
Bearbeitet: ezekiel gandham
am 2 Dez. 2017
plz send b coefficients for ieee14 bus 5units, ieee39 bus 10 units and ieee30 bus 6 unit systems to ezekielgandham123@gmail.com
asmaa nasef
am 4 Dez. 2017
Emmanuel Codjoe
am 27 Jul. 2021
plz send the power flow matlab code to ecooljoe@gmail.com
kalana agampodi
am 18 Okt. 2021
https://www.mathworks.com/matlabcentral/answers/23781-ieee-14-bus-power-flow-code#comment_1771566
POORNIMA JAYAPRAKASH
am 22 Jan. 2014
0 Stimmen
Thanks for Data file I need also Power flow solution code. Please help me .....
Sonu Kumar Bairwa
am 31 Jul. 2021
0 Stimmen
any one can send me matlab code for optimal pmu placement by using integer linear programming for line outage and normal condition case. please help me. please send code on gmail enggsonubairwa@gmail.com
3 Kommentare
Walter Roberson
am 31 Jul. 2021
Yes, I recognize that as a project that gets assigned every couple of years, so there is someone in the world who has programmed it in the past. If you could find someone who had already programmed it, and you could convince them to share the code with you, you would be all set. It is possible.
However, in practice... it is probably going to take you longer to find someone who has already done the work and convince them to share the code with you, then it would take you to program it yourself.
kalana agampodi
am 6 Okt. 2021
Bearbeitet: Walter Roberson
am 7 Okt. 2021
kalana agampodi
am 6 Okt. 2021
Check out the link I send I completed it.
I used Newton Raphson to get it to converge and also used fast decoupled power flow analysis and Q limit control.
Let me know if you have questions.
Good luck!!
Kategorien
Mehr zu Power and Energy Systems finden Sie in Hilfe-Center und File Exchange
Community Treasure Hunt
Find the treasures in MATLAB Central and discover how the community can help you!