Drive SampleClock to PFI signal as a sanity check.
Ältere Kommentare anzeigen
Hello! :)
I am doing some timing work and I would like to drive the internal sample clock on an NI USB-6259 board out to a PFI connection so I can sanity-check it using an oscilloscope.
I can find good MATLAB documentation on how to change the SampleClock to an external one, but I can't find out how to drive the internal SampleClock to an output.
How do you drive the internal SampleClock to a PFI output?
Thank you!
-Adam
Antworten (1)
Manisha
am 24 Jan. 2012
0 Stimmen
Hi Adam,
If you are uisng Session-based interface, you can use the R2012a prerelease and use the function
addClockConnection('Dev1/PFI1','external','ScanClock');
this would have the scan clock available at PFI1 of Dev1 for external use.
Hope that helps,
Manisha